Dip-Switch Settings; Functions - AERMEC VMF-E0X Manuel D'utilisation Et D'installation

Système vmf platine thermostat pour ventilo-convecteurs
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

DIP-SWITCH SETTINGS

Turn off the power to the unit.
This operation should be carried out in the installation
phase, by suitably trained and qualified personnel only.
The dip-switches are on the electronic board. They can
be used to obtain the following functions:
They can be used to obtain the following functions:
Position

Functions

Dip 1
ON
Cut-off valve PRESENT
OFF
Cut-off valve ABSENT
Dip 2
ON
Water probe upstream of the three-way valve
OFF
Water probe downstream of the three-way valve
Dip 3
ON
CONTINUOUS ventilation
OFF
THERMOSTATED ventilation.
Dip 4
ON
REDUCED BAND enabling
OFF
NORMAL BAND enabling
Dip 5
ON
Combination of Dip 5 and Dip 6
OFF
Dip 6
ON
Combination of Dip 5 and Dip 6
OFF
Dip 7
ON
Dead zone 2°C
OFF
Dead zone 5°C
Dip 8
ON
Input micro-switch used for thermostat season change
OFF
Input micro-switch used for thermostat enabling
Dip 6
Dip 5
**Type of system
OFF
OFF
2-Pipe System with Electric Heating Element
OFF
ON
4-pipe system
ON
OFF
2-pipe system with Plasmacluster/Bactericide lamp
ON
ON
2-Pipe System with Replacing Electric Heating Element (2T+2F)
SOME EXAMPLES:
VMF_E0 (default)
ON
1 2 3 4 5 6 7 8
SW
Reduced band
ON
1 2 3 4 5 6 7 8
SW
Functions dependent on the combination of 2 Dip
Water sensor upstream of the valve
ON
ON
OFF
1 2 3 4 5 6 7 8
Dead band 2°C
ON
ON
OFF
1 2 3 4 5 6 7 8
ON
OFF
SW
ON
OFF
SW
AVMFE0LJ 1704 - 6795744_00
Continuous ventilation
ON
1 2 3 4 5 6 7 8
SW
* Centralised control enabled
ON
1 2 3 4 5 6 7 8
SW
ON
OFF
ON
OFF
21

Publicité

Table des Matières
loading

Table des Matières