DIP-SWITCH SETTINGS
Turn off the power to the unit. This operation should be carried
out in the installation phase, by suitably trained and qualified
personnel only.
The dip-switches are on the electronic board.
They can be used to obtain the following functions:
Position
Functions
Dip 1
On
Cut-off valve PRESENT
Off
Cut-off valve ABSENT
Dip 2
On
Water probe upstream of the three-way valve
Off
Water probe downstream of the three-way valve
Dip 3
On
CONTINUOUS ventilation
Off
THERMOSTATED ventilation.
Dip 4
On
REDUCED BAND enabling
Off
NORMAL BAND enabling
Dip 5
On
Combination of Dip 5 and Dip 6
Off
Dip 6
On
Combination of Dip 5 and Dip 6
Off
Dip 7
On
Dead zone 2°C
Off
Dead zone 5°C
Dip 8
On
Input micro-switch used for thermostat season change
Off
Input micro-switch used for thermostat enabling
Dip 6
Dip 5
**Type of system
OFF
OFF
2-Pipe System with Electric Heating Element
OFF
ON
4-pipe system
ON
OFF
2-pipe system with Plasmacluster/Bactericide lamp
ON
ON
2-Pipe System with Replacing Electric Heating Element (2T+2F)
SOME EXAMPLES:
VMF_E1 (default)
ON
1 2 3 4 5 6 7 8
SW
Reduced band
ON
1 2 3 4 5 6 7 8
SW
Functions dependent on the combination of 2 Dip
Water sensor upstream of the valve
ON
ON
OFF
1 2 3 4 5 6 7 8
Dead band 2°C
ON
ON
OFF
1 2 3 4 5 6 7 8
ON
OFF
SW
ON
OFF
SW
AVMFE1LJ 1704 - 6795741_00
Continuous ventilation
ON
1 2 3 4 5 6 7 8
SW
ON
1 2 3 4 5 6 7 8
SW
ON
OFF
ON
OFF
21