3-7-1. 10~20K
Programs available list for parameter 1:
Code
Description
01
Output voltage
02
Output frequency
03
Voltage range for bypass
04
Frequency range for bypass
05
ECO mode enable/disable
06
Voltage range for ECO mode
07
Frequency range for ECO mode
08
Bypass mode setting
Maximum battery discharge time
09
setting
Programmable output setting
10
Shutdown point for programmable
11
output
12
Neutral loss detection
13
Battery voltage calibration
14
Charger voltage adjustment
15
Inverter voltage adjustment
16
Output voltage calibration
17
Phase auto adapt enable/disable**
*Y means that this program can be set in this mode.
**This function allows UPS input phase sequence more flexible. If it is enabled, UPS can adapt several kinds of phase
difference even it works like a single phase UPS. If it is disabled, UPS only can work under standard input phase sequence
among L1, L2, and L3. Please refer to program 17 below for more details about LCD setting.
01: Output voltage
Interface
02: Output frequency
Interface
60 Hz, CVCF mode
50 Hz, Normal mode
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 14 AA 59 203 46
Bypass /
No Output mode
Y*
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
Setting
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three
options in parameter 2:
50.0Hz: The output frequency is setting for 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz.
ATO: If selected, output frequency will be decided according to
the latest normal utility frequency. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the
output frequency will be 60.0Hz. ATO is default setting.
AC
ECO
CVCF
mode
mode
mode
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Battery
Battery
mode
Test
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
76