Chart I: Functions of potentiometers and hook switches
Switch/Pot.
Functions
Potentiometer for FLC-settings:
P1 for No. 1 pump
P2 for No. 2 pump
P3 for No. 4 pump
P4 for No. 3 pump
P8 to set pump stop time delay (0 – 2 min)
P9 to set pump stop time delay on low water cut-out (0 – 2 min)
Setting pressure setpoints (see pump duty chart, Fig. 5)
p
max 2
P5 – base-load pump switch-off pressure
p
max 1
P6 – base-load pump switch-off pressure
p
P7 – switch-on pressure for all pumps
min
S 1
Effect reversal for input low-water cut-out:
S 1 open: Plant runs on closed contacts on terminals WM,
S 1 closed: Reverse action.
S 2
Test run:
S 2 open: Test run activated
S 2 closed: Test run deactivated
S 5
Sensor input:
S 5 open: Plant stops on opening of sensor contacts (without fault signal)
S 5 closed: Plant runs on opening of sensor contacts (oll pumps)
S 3, 4, 7
Setting to the number of controlled pumps:
No. of pumps:
1:
2:
3:
4:
0 ¡ open, 1 ¡ closed
Motor fuses, 6.3 diam. x 32 mm, 16 amps inert, 440 V
for pumps:
F1-3
P1
F4-6
P2
F11-13
P3
F14-16
P4
F7
Control circuit fuse: 6,3 diam. x 32 mm, 0.1 mA, 250 V
Chart II: Settings of hook switches and potentiometers for different applications
Switch/Pot.
S 5
S 2
S 1
* 0 ¡ open, 1 ¡ closed
Technical modifications reserved !
plant stops on open contacts on terminals WM
Hook switch positions:
Phases:
Fuses:
(Fig. 2/3)
S 3
S 4
1
0
0
1
0
0
0
0
L01
L02
L03
F01
F02
F03
F04
F05
F06
F11
F12
F13
F14
F15
F16
Pressure boosting
*0*
0
0
Set FLC value to motor name plates
2
0.5
S 7
0
0
1
0
Fire services
*1*
0
0
2
0.5
ENGLISH