ASC 2500 G LE / ASC 3500 G LE
Problem
The display shows
"Fill up UV additive recep-
"
tacle!
The display shows
"Fill up fresh oil
receptacle!"
The display shows
"External vessel empty or
closed valve. Check!
The display shows
"Change the equipment
drier filter! Carry on?
The display shows
"Change the vacuum pump
"
oil! Carry on?
The display shows
"Printer not in line! Carry
"
on?
The display shows
"Error 01"
The display shows
"Error 02"
The display shows
"Error 03"
EN
Cause
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
This message appears dur-
ing the filling process if there
is not enough fresh oil in the
container to finish the pro-
cess.
This message appears at the
start or during the filling of
the internal refrigerant con-
"
tainer if the set refrigerant
quantity cannot be attained.
This message appears when
you switch on the
AirCon Service Center.
"
This message appears when
you switch on the
AirCon Service Center.
Message indicates a printer
fault.
It was not possible to reduce
the pressure sufficiently
before the pressure increase
test.
Pressure increased again
with pressure increase test. It
is not possible to reduce
pressure sufficiently.
No data is coming from the
refrigerant scale.
Troubleshooting
Remedy
Fill up the UV additive recep-
tacle.
Top up the fresh oil container
with a suitable oil type.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
Change the internal filter as
soon as possible (chapter
"Changing the dryer filter" on
page 113). To skip this, press
ENTER.
Change the vacuum pump oil
as soon as possible (chapter
"Changing the vacuum pump
oil" on page 117). To skip
this, press ENTER.
Check if there is paper in the
printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.
Check the air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.
Check the scale.