PRESSURE SWITCH ADJUSTMENT
1 - Connect the Sentronic connector according to page 13
Do not apply pressure to the input port.
2 - Turn potentiometer P6 clockwise to its maximum value (there is no limit stop).
3 - Connect a LED with resistor 4,7 KΩ between pin 7 and pin 2 or pin 7 and pin 1 according to
the pressure switch option.
4,7 kΩ
7
(+ 24V)
PNP
4 - Apply a set point according to the half window size (without pressure at the input of the valve)
Example : for a 0-3 bar SENTRONIC you need a ± 70 mbar window size.
0,07 : 3 = 2,3 % of 10 volts. Apply a set point of 0,23 V.
5 - Turn P6 counter clockwise until the LED status is changed.
OPTION : SET POINT - RAMP (010 610)
It allows to transform a set point bounce into a set point ramp. Rising or falling ramps can be adjusted
separately by means of a potentiometer.
The set point ramp is used to retard the valve's reaction and avoid overshoot.
VR1 : Ramp time for rising set point 0 - 4 sec
VR2 : Ramp time for falling set point 0 - 4 sec
Voltage input
0 . . . 10 V : 200 kΩ input resistance
0 . . . 20 mA : 500 Ω shunt resistance
Current input
The span and zero point must be adjusted as shown on page 15
OPTION : EXTERNAL FEEDBACK VALUE INPUT (consult us)
Instead of the internal pressure sensor, an external sensor for pressure, force, speed, position, etc. . .
is used. The external feedback value is supplied to pin 6 of the connector.
Voltage input
0 . . . 10 V : 100 kΩ input resistance
0 . . . 20 mA : 500 Ω shunt resistance
Current input
4 . . . 20 mA : 500 Ω shunt resistance
Current input
The span and zero point must be adjusted as shown on page 15
7
2
(0V)
(0V)
4,7 kΩ
(+ 24V)
NPN
Pressure
VR1
Set point
GB
1
VR1
VR2
VR2
17