GB
PROPORTIONAL GAIN :
You can use gain adjustment in a range from 1 to 11with potentiometer P7.
Proportional gain is factory adjusted to maximum (11).
You can use proportional gain to reduce oscillation and overshoot.
To increase the gain, turn P7 clockwise.
To becrease the gain, turn P7 counterclockwise.
PRESSURE SWITCH OPTION FOR THE SENTRONIC
Ø PORT
(Ø diameter)
G 1/8 (3 mm)
G 1/4 (6 mm)
G 1/2 (12 mm)
G 1
(20 mm)
NOTE
The output signal tolerance is adjusted at ± 5% PMR at factory.
This tolerance can be varied from ±1.4 % to ± 6 % max. with potentiometer P6
The maximum output current of pin 7 is 500 mA, at 24 V DC. See operating diagram, page 13.
16
PRESSURE SWITCH
OPTION
Ground reference on pin 7
if setting is reached
Signal 24V DC on pin 7
if setting is reached
Signal 24V DC on pin 7
if setting is not reached
Ground reference on pin 7
if setting is not reached
100%
PMR
Setting not
reached
5%
0
0,5V
-5%
1mA
RELAY ACTIVATED IF
CONNECTION IS
TRANSISTOR
BETWEEN :
Open collector
24V and pin 7
Open collector
Ground and pin 7
Open collector
Ground and pin 7
Open collector
24V and pin 7
Setting not
reached
10V
20mA
USED
LOGIC
Signal LOW
NPN
Signal HIGH
PNP
Signal HIGH
PNP
Signal LOW
NPN
Setting
reached
CODE
OPTION
010 539
010 579
010 612
010 613