Function and features
The AS-i AirBox is a slave in the AS-i system (AS-i profile S 7.F). It is the
connection between the two dual sensors, the two pneumatic outputs
and the AS-i master.
• Integrated sensor supply (a total of 100mA per module)
• Plug-in sensor connection
• AS-i connection via EEMS module lower part
• Connection to pneumatic system via push fit tube connector Legris
3000 / 8mm, outside calibration according to CETOP standards RP 54 P
• Operation with compressed air of 2...8bar including any pressure
peaks (Pressure peaks >8bar can cause permanent leaks and irrepa-
rable damage of the AirBox).
• External voltage supply 24V DC PELV
flat cable yellow
flat cable black
I-2, AS-i PWR, O-3
pneumatic
outputs O-3/O-4
manual override 1 for O-3
Mounting
Address assignment by means of the addressing unit.
Fix the module onto the addressing unit. Assign a free address between
1 and 31; the factory preset is 0.
Mount the module onto the wired module lower part of the AS-i net-
work, tightening torque 0.8Nm.
6
I-1/2
exhaust 3 [R]
I-1
I-3
I-3/4
I-4, O-4
Ext. PWR
compressed air 1 [R]
manual override 2 for O-4