Chapter 8: Specifications
SYSTEM SPECIFICATIONS
Model Number
PRO750RT2U PRO1000RT2U PRO1500RT2U PRO2000RT2U
Topology
750VA
Maximum Power Capacity
525W
Number of Phase
Nominal Voltage
Acceptable Input voltage
Voltage Range
Frequency Limits
Low Voltage Transfer Point
151V resets to Utility Power at 146V or lower
High Voltage Transfer Point
Protection
Power Cord (10ft)
OUTPUT NON-BATTERY OPERATION
Voltage Range
Voltage Regulation
Frequency Range
Efficiency (Line Mode)
OUTPUT BATTERY OPERATION
Waveform Type
Nominal Voltage
Voltage Regulation
60Hz, ±0.5Hz (unless synchronized to utility)
Frequency
Transfer Time
AC Mode: 110% for 1-minute then shutdown, 150% Shutdown Immediately
Overload Capacity
DC Mode: 110% for 20-seconds then shutdown, 150% Shutdown Immediately
Protection
Over-Current, Short-Circuit Protected and Latching Shutdown
Receptacles (NEMA)
REGULATORY COMPLIANCE
Safety and Approvals
cTUVus (Conforms to UL1778 5th Edition & CSA 22.2 no. 107.3-
14 / R: 2014), FCC Class B, CE certified, RoHS2 (EU Directive
2011/65/EU & 2015/863/EU)
28
Line-Interactive, Simulated Sine Wave
1000VA
1500VA
700W
1050W
INPUT
Single (1 2W +G)
120VAC
0 - 150VAC
90 - 150VAC
60 Hz, ±6Hz
89V resets to Utility Power at 94V or higher
Resettable Circuit Breaker
NEMA 5-15P
NEMA 5-20P
103 - 136VAC
120VAC: ±13.3%
60Hz: 54 - 66Hz
>96% (Full Load)
Simulated Sine Wave
120VAC
120VAC ±5% (until Low Battery Warning)
6-10 ms Typical
6: 5-15/20R
8: 5-15R
1: L5-20R
Battery Type
Typical Recharge Time
Typical Battery Life
Battery Module Part #
2000VA
Runtime: Full Load (minutes)
1400W
Runtime: Half Load (minutes)
UPS Surge Energy Rating
Surge Current Capability
Response Time
Surge voltage let-through (as a
percentage of an applied ANSI
C62.41 Cat. A ±2 kV)
Noise Filter
Audible Noise at 1 m (3 ft.)
Network/Phone/Fax/Modem
transient voltage surge protection
Coax transient voltage surge
protection
Operating Temperature
Operating Elevation
Operating/Storage Humidity
Storage Temperature
Storage Elevation
Size - Net
L X W X H
Weight - Net
Size - Shipping
L X W X H
Weight - Shipping
BATTERY SYSTEM
Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid
8-hours to 90% capacity from a full load discharge
3 to 5 years. Environmental factors do affect battery life. High
temperatures, poor utility power, and frequent, short duration
discharges have a negative impact on battery life.
BM0072
BM0073
5
4
15
14
SURGE PROTECTION AND FILTERING
960 J
6500 Amps total (one time 8 to 20us waveform)
0 ns (instantaneous) normal mode; <5 ns common mode
< 0.30%
>45db normal and common mode EMI/RFI suppression
<45 dBA
10/100/1000 Base-T network, single line phone, Fax or Mo-
dem. 1-in / 1-out combo RJ11/45 connectors
Cable modem , CATV converter, DSS receiver, DVR.
1-in / 1-out
ENVIRONMENTAL
0 to 40C (+32 to +104F)
0 to 3000m (0 to +10,000 ft)
5- 95% Non-Condensing
-15 to +45C (+5 to +113F)
0 to 15,000m (0 to +50,000 ft)
PHYSICAL
16.1 X 18.9 X 3.4"
410 X 480.6 X 86.2 mm
31.3 lbs
35.7 lbs
14.2 Kgs
16.2 Kgs
22.4 X 21.7 X 9.4"
570 X 550 X 240 mm
37.5 lbs
41.9 lbs
17.0 Kgs
19.0 Kgs
BM0074
BM0075
4
4
14
14
20.1 X 18.9 X 3.4"
510 X 480.6 X 86.2 mm
48.7 lbs
62.8 lbs
22.1 Kgs
28.5 Kgs
26.4 X 22.4 X 9.4"
670 X 570 X 240 mm
56.4 lbs
70.5 lbs
25.6 Kgs
32.0 Kgs
29