Programming Instructions
KINAX N702-INOX HART via the HART Field Communicator 475
KINAX N702-INOX HART may be very easily program-
med via commercially available HART field communi-
cators (e.g. Emerson type 475).
1. Commissioning
1.1 Connection
Connect the HART field communicator 475 directly to
the 4...20mA 2-wire signal line of KINAX N702-INOX
HART. The measuring circuit must have a minimum
apparent resistance of 240Ω.
R
L
Transmitter-
power supply
unit
24V
1.2 Switch on
Switch on HART Field Communicator 475
Select operating mode HART
Confirm with YES
All manuals and user guides at all-guides.com
HART
Communicator
Your are now in the display mode
1.3 Set zero point (43 Set Primary Variable Zero)
Select Device setup
Select Diag/Service
Select Zero trim
Set zero point and confirm with OK.
9