3. Programming use case 2:
Set zero point
In application case 2, the measuring range of 4...20mA
is symmetrically apportioned between two firm angular
positions (e.g. -60° to +60°).
3.1 Programming mode
Select Device setup
Select Detailed setup
Select Signal conditions
3.2 Set zero point
Set zero point according to section 1.3
All manuals and user guides at all-guides.com
3.3 Set measuring range
Select Primary Variable Upper Range Value (PV URV)
Set desired angle range (z.B. 60.00°)
Select Primary Variable Lower Range Value (PV LRV)
Set desired angle range (z.B. -60.00°)
3.3 Definition of direction of rotation
The direction of rotation is defined via setting the algebraic
sign +/- in URV/LRV.
cw / ccw
-60° (PV LRV [37])
60° (PV LRV [37])
Zero point (43)
60° (PV URV [36])
-60° (PV URV [36])
11