FIRE damper type FDMD, is in all variants classified:
as
EN 15650.
Installation in a solid wall construction
1
Fire damper FDMD
2
Mortar or gypsum with min. density 800 kg/m
or another approved  fire sealing system for
damper installation
Installation in a solid wall construction
1
Fire damper FDMD
2
Stuffing box (mineral stone wool min. density
140 kg/m ) or another approved fire sealing
system for damper installation
3
Fire protection mastic Promastop P,K or
equal min. thickness 1 mm
Installation in a solid wall construction (Weichschott system)
1
Fire damper FDMD
2
Fire resistant board
3
Fire stop coating thickness 1 mm
 Used materials ­ example:
2 ­ Hilti CP673 PF
3 ­ Hilti CP673
All manuals and user guides at all-guides.com
 acc. EN 13501­3 and tested acc. EN 1366­2 and acc.
1
Min. 50