All fire dampers has to be closed during installation process. The damper body should not be deformed
in the course of bricking in. Once the damper is built in, its blade should not grind on the damper body
during opening or closing.
10. To  provide  needed  access  space  to  the  control  device,  all  other  objects  must  be  situated  at  least
350 mm from the control parts of the damper. Inspection hole must be accessible.
11. Electrical components, wiring diagrams.
~
­
+
1
2
Tf1
Tf2
Tf3
12.   B efore entering the dampers into operation after assembly and after sequential revisions, checks and
functionality tests of all designs including operation of the electrical components must be done. After
entering  into  operation,  these  revisions  must  be  done  according  to  requirement  set  by  national
regulations.
13.   B efore entering the dampers into operation after their assembly and by sequential checks, the following
checks must be carried out.
 
Visual inspection of proper damper integration, inside damper area, damper blade, contact surfaces and
silicon sealing.
Inspection  hole  disassembly:  release  the  covering  lid  by  removing  the  two  screws  in  the  corners  of
inspection hole. Then remove lid from its original position.
All manuals and user guides at all-guides.com
Connection through
an insulation transformer.
S1
S2
S3
S4
S5
<5°
BAE72B­S
LED
N L1
1
2
S1
S2
S3
<5°
BAE72B­S
Tf1
Tf2
Tf3
LED
BLF24­ST­T: Design with connector plugs for communication
to network and communication device BKN230­24
S6
<80°
Parrallel connection of other driver is possible.
Pay attention to the power input data.
For separation from the mains, a device that
insulates polar conductors must be at disposal
(Minimum distance between contacts ­ 3 mm).
S4
S5
S6
<80°
Parrallel connection of other driver is possible.
Pay attention to the power input data.
13