Télécharger Imprimer la page

Mandik FDMD Mode D'emploi page 10

Publicité

1.)  All fire dampers has to be closed during installation process.
2.) The control mechanism has to be protected (covered) against damage and pollution during installation
 
process.
3.) Min. gap for installation (installation opening) is 25 mm (circular dimension
4.) Installation gap  must  be  filled  by  approved  material  perfectly  in  all  the  installation  space  volume
 
(installation gap).
5.)
The  distance  between  the  fire  damper  and  the  construction  (wall,  ceiling)  must  be  minimum  75  mm
according  to  EN  1366­2.  In  case  that  two  or  more  dampers  are  supposed  to  be  installed  in  one  fire
separating construction, the distance between the adjacent dampers must be at least 200 mm according
to EN 1366­2 paragraph 13.5.
6.) Installation openings.
All manuals and user guides at all-guides.com
9
D + 50 mm).
Ø