ATEX Directive they are suitable for use in the following types of zones in explosion
hazardous areas:
for combustible gases, vapors and mist: zone 2
for combustible fibers and dust: zone 22
The parts used are all manufactured from corrosion resistant materials and are resistant to
the effects of most common chemicals.
5.
Technical Data
Explosion safety category:
Protection against ignition:
Conformity:
Standards applied:
Ambient temperature:
Material housing:
Dimensions (L x W x H):
Light source:
Light color:
Power supply:
Power consumption:
Ingress protection level:
Beam angles:
Rotation angle:
Light strength:
Circumstances of use:
Electrical connection:
Ambient temperature:
Weight:
6.
Marking
The SpotLED complies to the European Directives for EMC and ATEX and integral to the
Low Voltage Directive. With regard to explosion safety the SpotLED has been designed and
manufactured on the basis of the essential health and safety requirements of European
Directive 2014/34/EU (ATEX 114) relating to Group II Category 3GD. Harmonized European
construction standards have been applied fulfilling the essential requirements of the
Installation manual AR-040 SpotLED
II 3GD
Ex ec IIC T4 Gc, Ex tc IIIC T135˚C Dc
European Directive 2014/34/EU (ATEX) and 2014/30/EU (EMC)
EN 60079-0:2018, EN 60079-7:2015 / A1:2018 and
EN 60079- 31:2014
-30 ˚C to +50 ˚C
Die cast aluminum housing and stainless steel bracket coated
in the same color. Polycarbonate impact-resistant safety glass
120 x 62 x 87 mm
Cree 3 Watt PowerLEDs (5x), 780 Lumen
Neutral white (~6700 K)
12 - 30 VDC
500 mA @ 24 VDC, 950 mA @ 12 VDC
IP67 according to EN 60529
10º to 38º (depending on the optics used)
-50º to +105º
780 Lumen
Exterior and interior use
Fixed cable, length 5 meters (brown = +24 VDC, white = 0 V,
green = ground / earth)
-30 ˚C to +50 ˚C
540 grams
E
12-2024
9 / 40