directives. For more details refer to section 5 "Technical data" or to the EU Declaration of
Conformity on the last page of this manual.
E
SpotLED AR-040/110 - 5 x 10°
II 3 G Ex ec IIC T4 Gc, II 3 D Ex tc IIIC T135°C Dc
Cert. Artidor 24ATEX9999 X
Example of an AR-040 SpotLED-EX label
7.
Installation instructions
•
Installation of explosion-safe equipment such as this product must be carried out by
personnel specially trained and qualified to do this, following the relevant requirements
of the installation standard EN 60079-14.
•
For the installation and use of this product the relevant safety regulations and also the
generally recognized latest state of the technology apply.
•
During assembly, care must be taken that the framework, screws and surface are strong
enough to take the weight of the SpotLED.
•
Isolate power from the electrical supply cable prior to installation.
•
Mount the SpotLED on a metal frame or structure connected with ground (equipotential
bonding).
•
Install the connection cable and make sure that it is protected from mechanical and
chemical influences.
•
Connect the end of the cable in a proper way to an external connection box and ensure
this is done professionally. The connection box is not supplied. Use a connection box
that it is suitably protected for the (explosion hazard) classification of the surroundings in
which it will be used.
•
The connection cable has three cores for the following connections:
Green / yellow:
Blue:
Brown:
8.
Maintenance
For the maintenance of the SpotLED the requirements as stated in EN 60079-17 apply.
If the SpotLED and the connection cable are no longer in good condition or are very dirty or
damaged they must be repaired or cleaned immediately.
Installation manual AR-040 SpotLED
10 / 40
Artidor Explosion Safety, Emopad 38
Year 2024
Earth or equipotential bonding
Neutral (-)
Positive (+)
5663 PB Geldrop, The Netherlands
-30 °C < Ta < +50 °C
12-30 VDC, 950 mA
Lot. No.: AS249999
12-2024