Technical Data; Intrinsically Safe Switch Circuits; Safety Instructions - Cooper Crouse-Hinds CEAG GHG 511 .9 Série Mode D'emploi

Fiches et prises pour atmosphères explosives
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2

Safety instructions

The multiple plug and socket
systems 7-pole (GHG 511 .7. /
GHG 592) and 21-pole (GHG 511 .9 /
GHG 591) are not suited for use
in Zone 0.
The operations must be carried out by
electrical suitably trained in hazardous
area with knowledge of increased safty
explosion protection
IEC 60079-14.
The temperature class and type of
protection stated on the apparatus shall be
observed.
To ensure adherence to the temperature
class stated on the type label of the
apparatus, the permissible ambient
temperature, the rated terminal cross
section and the self-heating of the
apparatus, that is mainly due to the power
dissipation, shall be taken into account
(test criterion for the self-heating is an
overload of 10%).
Modifications or changes to the plug and
socket systems are not permitted.
They shall be used for their intended
purpose and in a perfect and clean state.
Only original COOPER CROUSE-HINDS
parts may be used as replacements and
for repairs.
Repairs that affect the explosion
protection, may only be carried out by
COOPER CROUSE-HINDS or by a
qualified electrician in compliance with
the respective national regulations.
Prior to being put into operation, the
plug and socket systems shall be checked
in accordance with the instructions as per
section 6.
The sockets may only be used with the
associated COOPER CROUSE-HINDS
plugs in undamaged condition.
The 7-pole wall socket is safeguarded by
an interlocking switch and can, therefore,
not
be switched on if the plug is not inserted.
The plug of the 21-pole plug and socket
may not be inserted into the 21-pole
sockets and coupler or withdrawn from
them while they are live (see also Section 5).
Before initial operation, any foreign matter
shall be removed from the apparatus.
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions included in these
operating instructions, that, like this text,
are set in italics, shall be observed!
Explosion-protected plugs and sockets, 7-pole
GHG 511 .7.. / 592 and 21-pole GHG 511 .9.. / 591
1

Technical data

1.1
Plugs and sockets, 7-pole
Marking acc. to 94/9/EC and directive:
EC type examination certificate:
Rated voltage:
Rated current:
Perm. short-circuit back-up fuse:
Switching capacity AC 3 :
Switching capacity AC 15:
Switching capacity DC 13:
Permissible ambient temperature:
Other temperatures possible with special versions.
Perm.storage temperature in original packing:
Degree of protection to EN/IEC 60529:
with closed and secured hinged cover as well as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entries:
Wall socket (GHG 511 47)
Plug ( GHG 592 2)
Supply terminal:
Switch contact block of wall socket
Pin for plug
Test torques:
Cap nut of the cable entry M40
Cover- and plug screws:
Terminals
Weight (standard version):
1.2
Plugs and sockets, 21-pole
Marking acc. to 94/9/EC and directive:
EC type examination certificate:
Wall socket, coupler, plug
Flange socket
Rated voltage:
Max. rated current:
Perm. short-circuit back-up fuse:
Permissible ambient temperature:
Other temperatures possible with special versions.
Perm.storage temperature in original packing:
Degree of protection to EN/IEC 60529:
with closed and secured hinged cover as well as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entries:
Wall socket
Plug
Coupler
Supply terminal:
Contact pin for sockets and coupler
Pin for plug
Test torques:
Cap nut of the cable entry M40
Cover and plug screws
Weight:
Wall socket
Plug
Flange socket
Coupler
1.3

Intrinsically safe switch circuits:

Max. safe voltage U
:
m
II 2 G Ex e II C T5 / T6
II 2 G Ex de [ia] II C T5 / T6
PTB 00 ATEX 1109
up to 400 V, 50/60 Hz
max. 16 A
without therm. protect.
max. 16 A
400 V /16 A
400 V / 6 A
24 V /
6 A
-20° C up to +40° C (standard version)
-40° Cup to +80° C
IP 66 (standard version)
I - is complied with by the devices
(standard version)
2 x M40
1 x Ø 19 - 28 mm + 1 x screwed plug
Ø 9 - 17 mm
Cross section
2 x 1.5 - 4.0 mm²
1 x 1.0 - 2.5 mm² *
* crimp or soldered connections
5.0 Nm
2.5 Nm
2.5 Nm
Wall socket
approx. 2.20 kg
II 2 G Ex e II C T5 / T6
II 2 G Ex de [ia] II C T5 / T6
PTB 00 ATEX 1109
PTB 00 ATEX 1108 U
up to 250 V, 50/60 Hz
10 A
without therm. protect.
max. 16 A
-40° C up to +80° C
-40° Cup to +80° C
IP 65 (standard version)
I - is complied with by the devices
(standard version)
1 x M40 (Ø 19 - 28 mm)
Ø 19 - 28 mm
Ø
9 - 27 mm
Cross section
1 x 1.0 - 2.5 mm² *
1 x 1.0 - 2.5 mm² *
* crimp or soldered connections
5.0 Nm
2.5 Nm
(standard version)
GHG 511 47
approx. 1.79 kg
GHG 591 2
approx. 0.70 kg
GHG 591 4
approx. 0.43 kg
GHG 591 3
approx. 0.77 kg
690 V
eff
Safe galvanic isolation from all other circuits
and earth
Cooper Crouse-Hinds GmbH
with therm. protect.
max. 25 A gL
230 V / 8 A
230 V / 0,4 A
Stripped wire length
6 mm
13 mm
Plug
approx. 0.30 kg
with therm. protect.
max. 25 A gL
Stripped wire length
13 mm
13 mm
7 7 7 7 7