HOT AIR OUTLET
GRID
BEAN
BEAM
INSULATION
AMBIENT AIR
The thermostat engages the pump only when the water reaches sufficient temperature in the boiler and the flow
pipe. Illustrations 2 and 3 show connection of boiler into the central heating system. The H height secures
sufficient pressure in the system in order to achieve good circulation through the heating bodies. A water boiler
can be installed into the system (it is advisable to do so). A boiler can secure natural (gravitational) circulation
independent of the pump. The water boiler is to be installed above the fireplace level with as low water circulation
resistance as possible (short pipes with elevation towards the boiler).
Prior to putting into operation (prior to first firing), check if the heating system is filled with water and well aired.
Open all shutters. Engage the circulation pump.
Enable access on the back of the fuel fireplace because of maintenance (on the connection of the conduits of the
central heating with the cattle).
The installation of the thermal product must be in compliance with all current norms and provisions as well as with
applicable laws. Fitting, connecting, putting into operation and testing for proper operation must be carried out in
accordance with the professional rules by authorised professionals while fully observing the current norms at the
national, regional and municipal levels of the country where the device is being fitted. Fitting may be performed
only by authorised professionals who are required to issue a completed and verified certificate/work order to the
customer. The customer is required to keep such certificate/work order and present it to the manufacturer at its
request as the proof that the installation of the thermal product was carried out by an authorised professional.
The company Plamen d.o.o. will not be held responsible in case of breaching the above and will not be
liable for any difficulty in the operation of the product and cost arising from this if the thermal product
was not installed by an authorised professional.
Fireplace installation
The fireplace insert is designed for encasing in masonry enclosure.
The fireplace insert shall be installed only by qualified persons or companies specialised for such works. When
installing the fireplace, make sure that all applicable regulations and standards, as well as these instructions
regarding the size of the heated space, flue pipes, chimney, fresh air supply to support combustion, air circulation
around the fireplace and recirculation from the heated space and fire protection are fully complied with.
Figure 1 shows an example how to encase a fireplace.
When coating the fireplace insert with elements made of stone, ceramics or similar (non-combustible) materials,
make sure that:
- air circulation is ensured between fireplace insert and the masonry enclosure wall. To
achieve this, minimum distance of 5 cm shall be provided between the fireplace insert and
the enclosure;
- Air supply and exhaust are provided below the insert and above the insert respectively,
through grids of a total area of 1000 cm2. (e.g. 3 grids 25 x 15 cm);
FLUE PIPE
Ø180 mm
INSULATION
WALL
FRESH AIR
SUPPLY GRID
BASE
22
min 50 mm
min 50 mm
min 50 mm
Figure 1