• When testing capacitors or cables, ensure complete discharge at the
conclusion of the test. Momentary shorting of terminals may not
suffice, as dielectric absorption can cause voltage to reappear shortly
after removing the short. To mitigate this, maintain the short for an
extended period, such as ten seconds, before confirming
complete discharge.
Initial Test
We advise conducting daily tests on the unit according to the
following procedure:
1. Set VOLTAGE ADJUST knob
to zero.
2. Ensure the main power
is OFF.
3. Short the high-voltage
output to the ground clip.
4. Turn on the main.
It's important to note that due to the inherent resistance in the
secondary winding of the transformer, achieving the 95mA threshold
may not be possible at voltages lower than approximately 250V.
1.800.561.8187
www.
.com
5. Gradually increase
the voltage.
6. Observe for tripping off,
which should occur at a
very low voltage if the unit
is functioning properly.