Heat Pump lockout temperature (T
activating Heat Pump lock. If the outside temperature is below the lock temperature set,
the indoor unit (in ventilation mode) and Auxiliary Heat will be activated until the outside
temperature reaches a differential of +5ºC with regard to the set lock temperature and the
Delta Off (T
Ventilation mode to Heat Pump mode there will always be a 90-second delay.
EN
T
out
- 20 ºC
Heat Pump Locked
T
: Outside temperature
out
There are 3 outside Temperature scenarios:
T
< T
outside
Lock Heat Pump
T
Lock Heat Pump
T
Lock Heat Pump
Note: for units that do not have the "Outside Temperature" mode parameter, the outside
temperature provided by the Cloud will be taken as the default.
Note: the auxiliary heat and heat pump lock outside temperature difference will be at least
ΔT
= 6ºC, and priority will be given to heat pump lock temperature over auxiliary heat lock
min
temperature.
Digital input
Allows you to activate or deactivate this function and change:
Activation. Allows to set the input as:
a.
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
b.
Activation by edge: the status is punctual, only the on/off is sent when the opening or
closing condition is met for the first time.
Settings. Allows you to set the input as normally open or normally closed.
20
) defined in Auxiliary Heat is surpassed. When the indoor unit switches from
off
Range: -20°C (-4°F) / 4°C (39°F) in steps of 2ºC (3.6ºF). Default: -6ºC (21ºF).
T
Lock Heat pump
+ ΔT = 5 ºC
< T
Lock Aux.Heat
< T
< T
outside
Lock Aux.Heat
< T
< T
Lock Aux.Heat
outside
). It is used to set an outside temperature for
Lock Heat Pump
4 ºC
0 ºC
Heat Pump Unlocked
Demand
Indoor unit
ON
ON (FAN Max.)
OFF
ON (FAN Min.)
ON
ON (Set Mode)
OFF
OFF
ON
ON (Set Mode)
OFF
OFF
* Auxiliary Heat active only for Heat mode and Auto mode.
Auxiliary
Heat Pump
Heat
OFF
ON
OFF
OFF
ON
ON*
OFF
OFF
ON
OFF
OFF
OFF
18 ºC

Publicité