SETTINGS FROM AIRTOOLS ON AIRZONE CLOUD
Auxiliary Heat
It is used to activate or deactivate this function and to set configurations:
•
Delta On (T
). Offset applied to the setpoint temperature to activate auxiliary heat.
on
Range: -4ºC (-7.2°F) / -1.5ºC (-2.7°F) in steps of 0.5ºC (0.9ºF). Default: -2.5ºC (-4.5ºF).
•
Delta Off (T
). Offset applied to the setpoint temperature to switch off auxiliary heat.
off
Range: -0.5ºC (-0.9°F) / -1.5ºC (0.9°F) in steps of 0.5ºC (0.9ºF). Default: -0.5ºC (-0.9ºF).
- 4 ºC
ΔT
T
amb
Auxiliary Heat ON
T
: Zone ambient temperature
zone
•
Delay time. It configures the delay time for the activation of Auxiliary Heat using selectable
values. Deactivated: 90-second delay.
•
Type of ventilation. It is used to choose between ducted heating or external auxiliary heat.
Ducted heating relies on the indoor unit ventilation to activate auxiliary heat, and in External
auxiliary heating the ventilation source is independent of the indoor unit.
Heat source lock
This activates or deactivates heat source lock depending on the lock outside temperatures
defined.
•
Auxiliary Heat Lockout Temperature (T
for locking Auxiliary Heat function activation. If the outside temperature is above the lock
temperature set, the Auxiliary Heat function will not be activated even if the activation
conditions are met (T
Range: -14ºC (7°F) / 18ºC (64°F) in steps of 2ºC (3.6 ºF). Default: 0ºC (32ºF).
T
out
- 14 ºC
Auxiliary Heat Unlocked
T
: Outside temperature
out
- 1,5 ºC
on
T
on
OFF
).
on
0 ºC
- 0,5 ºC
ΔT
off
T
off
Set-Point
ON
). It is used to set an outside temperature
Lock Aux.Heat
T
Lock Aux. Heat
Auxiliary Heat Locked
0,5 ºC
Auxiliary Heat OFF
EN
18 ºC
19