NV175 HIALT Handbook
Environmental Specifications:
Description
Use
Temperature
Humidity
Altitude
Pressure
Orientation
Material Group
Pollution Degree
Overvoltage Category
Class
Weight
IP Rating
Note: fan models require a 50mm gap at the input and output ends.
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth - 2.25 - 2.35Kvdc.
*Primary mains circuits to secondary:4.25-4.35kVDC.
Outputs to earth are isolated to 200VDC.
*Important Note: This test is not possible with Y capacitors fitted to the unit as damage to these capacitors will occur.
It is also necessary to short circuit the outputs together and to earth
Safety Approvals:
UL60950-1, UL62368-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC / EN60950-1 – CE mark.
CE marking when applied to any NV175 product indicates compliance with the Low Voltage Directive
in that it complies with EN60950-1 and with the ROHS Directive.
IEC/EN 60950-1, IEC/EN62368-1, IEC/EN 61010-1 and IEC/EN 60601-1 - CB Report and Certificate
UL 61010-1, CAN/CSA 22.2 No. 61010-1-12
UL/CSA 60601-1/ANSI/AAMI ES 60601-1 - UL + C -UL approval
Fusing: Internal fuse (F1): T3.15AH, 250V, 5x20mm.
Symbols:
AC
DC
Danger, shock hazard
Note: All output voltages/variants may not be available as standard units, refer to datasheet for standard
product range. These (and other variants) may be available as non-standard or custom units, please contact
our sales team for details.
Operation
Indoor
0
0 to 65
C(derating 2.5% above 50°C)
Customer air models:
All, except Horizontal with PWB
uppermost
EARTH
Caution: See instructions for use
5 to 95% RH, non-condensing
-200m to 5000m for –H and –HR)
54kPa to 106kPa
Horizontal cover uppermost, PSU on its
side, Vertical with input lowest
IIIb
2
II
I
600g
IPX0
N – Neutral
Page 14 of 22
Storage
-
0
0
-40
C to +70
C
L – Live
17168 issue 9, October 2018