Unpacking and safety
Safety regulations
○ The electrical installation must be carried out in such a way that:
- The salt electrolysis and acid pump cannot work if the filter pump is not working. This is
endured by the flow switch. never use the aparatous without flow switch
- The acid pump and electrolysis can be turned off when the filter pump is running. This can
be done by pressing the on/off button on the bottom of the dosing pump or on top of the
electrolysis.
○ Addition of the pool chemicals should be done downstream of the pool accessories such
as heater, UV lamp, filter, and downstream of the measuring probes.
○ It is recommended to put the installation of the water treatment unit in bypass
configuration.
○ Install the water treatment unit on a solid base or against the wall (always vertically)
○ Always keep the product upright. If the product is tilted or placed on its side, the probes
will not be able to measure correctly, resulting in incorrect measurements
○ The product must be installed indoors.
○ The acid dosing device may not be used with hydrochloric acid (HCl).
○ Make sure that - in the event of a leak - the water or chemicals cannot run over the
installation. Resolve leaks immediately. Do not use leaking apparatous.
○ The electronics or the device itself must never be connected to an output of a frequency
converter or a frequency inverter
○ The dosing device must not be on the same power circuit as that of the frequency
regulator and frequency regulator it is at least 3m from the dosing unit.
○ Calibrate the pH and Rx probes before first use and at least every 3 months thereafter.
Verify "regularly" the chlorine content and pH with a color method.
2