4. Mounting
The EMBSIN 101 I can be mounted on a top-hat rail.
Note "Environmental conditions" in Section
"3. Technical data" when determining the place of
installation!
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 1).
Fig. 1. Mounting onto a top-hat rail 35 × 15 or 35 × 7.5 mm.
5. Electrical connections
Connect the leads acc. to the instructions on nameplate.
Make sure that all cables are not live when
making the connections!
Impending danger by high power supply
voltage!
Take care of current transformers!
Also note that, ...
... the data required to carry out the prescribed mea-
surement must correspond to those marked on the
nameplate of the EMBSIN 101 I (
input,
measuring output and
supply, see Fig. 6)!
... the resistance in the output circuit
– may not overrange the value
R
max. [kΩ] ≤
ext
(I
= current output end value)
AN
– with power supply via output leads (2-wire
connection, output 4 - 20 mA) dependent on
power supply H (12 - 32 V DC)
1000
600
0
0
H = Power supply [V]
R
max. [kΩ] =
ext
– may not underrange the value
R
min. [kΩ] ≥
ext
(U
= voltage output end value)
AN
... the measurement output cables should be twisted
pairs and run as far as possible away from heavy
current cables!
In all other respects, observe all local regulations when
selecting the type of electrical cable and installing them!
measuring
power
15 V
I
[mA]
AN
12
24
32
H [V] – 12 V
20 mA
U
[V]
AN
10 mA
– +
5 6 7 8
1 2 3 4
I
Fig. 2. AC power supply
-
R
ext
+
+
–
5 6 7 8
1 2 3 4
I
Fig. 4. Power supply via
output leads.
I
= Current measuring input
= Power supply
Measuring output
Output signal
5 6 7 8
4–20 mA
EMBSIN 101I
Works No.
Mat: 128349 / 4161903
0...5A 50/60 Hz
1 2 3 4
Measuring input
Measuring range
Measured quantity
Fig. 6. Declaration to type label.
– +
5 6 7 8
1 2 3 4
– +
I
Fig. 3. DC power supply.
– +
5 6 7 8
1 2 3 4
–
I
Fig. 5. DC, AC power supply,
in version with built-in
DC, AC power pack.
= Measuring output
Manufacturer
Conformity
3,7
230 VAC
marks
Power supply
7