Télécharger Imprimer la page

Watts LF007-FZ Manuel D'installation, De Maintenance Et D'essai page 3

Publicité

Servicing the Check Valves  
NOTICE
Before servicing, ensure the supply water is turned off or the shutoff 
valves are in the closed position. Open test cocks No. 2, No. 3, 
and No. 4 to relieve pressure inside the before removing the 
valve cover. 
1.  Remove the cover, then remove the retainer from the body valve. 
The check valve modules can be removed from the valve by 
hand or with a screwdriver. 
NOTICE
For Series 007 and LF007, sizes 
of the first and second check modules are not interchangeable. 
The heavier spring and smaller diameter seat belong with the first 
check module. Series 007M1 sizes ¾" to 1" and Series 007M2 
size ¾" have interchangeable seats and springs. 
2.  The check seats are attached to the cage with a bayonet type 
locking arrangement. Holding the cage in one hand, push the 
seat inward and rotate clockwise against the cage. Series 007M2/ 
LF007M2 size ¾" and LF007 have a pull­apart seat and cage. 
The seat, cage, and spring and disc assembly are individual 
components. 
3.  Clean and reassemble the disc assembly or, depending on its 
condition, discard and replace it with a new assembly from the 
repair kit. O­rings should be cleaned or replaced as necessary. 
4.  Reassemble the check valve module in the reverse order. Check 
modules are installed in the valve body with the seats facing the 
valve inlet. The modules must be securely in place before the 
retainer is replaced. On sizes ¾" to 1" this retainer may have to 
be tilted slightly into place. Replace the cover, and close all 
test cocks before returning the valve to service. 
1
" ­ 2", the seats and springs 
2
O­rings 
Spring 
Seat 
Disc 
Cover 
Cover 
O­ring 
Retainer 
Seat 
Seat 
O­ring 
Disc 
Assembly 
Spring 
Check 
Cage 
Cover 
Cover 
O­ring 
Check 
Cage
Body 
Retainer 
Body 

Publicité

loading

Ce manuel est également adapté pour:

Lf007 serie007 serie