3. Installing the indoor unit
1
2
4
5
* 8
7
0
en
F
H
15.5
0
25
50
75
100
117
125
142
192
242
279.5
292
C
A
C
D
A
D
4
3
6
* 9
* PKA-M·KAL only
Fig. 3-1
G
A
E
100 mm
A
K
I
J
Fig. 3-2
Sleeve
A
B
Hole
B
(Indoors)
C
Wall
D
E
(Outdoors)
E
Fig. 3-3
F
E
G
I
H
Fig. 3-4
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART NUMBER
*
1
2
3
4
5
*
* Wireless remote controller
6
* Remote controller holder
7
* Alkali batteries (size AAA)
8
* Tapping screw 3.5 × 16
9
0
3.2. Installing the wall mounting fixture (Fig. 3-2)
3.2.1. Setting the wall mounting fixture and piping positions
► Using the wall mounting fixture, determine the unit's installation position
(mm)
and the locations of the piping holes to be drilled.
Warning:
B
Before drilling a hole in the wall, you must consult the building contractor.
54
25
0
Mount board
A
12.5
37.5
Indoor unit
B
62.5
87.5
Bottom left rear pipe hole (ø75-ø80)
104.5
C
129.5
Bottom right rear pipe hole (ø75-ø80)
D
167
Knockout hole for left rear hole (75 × 480)
217
E
229.5
Bolt hole (4-ø9 hole)
F
264
292
Center measurement hole (ø2.5 hole)
G
308.5
311
Tapping hole (75-ø5.1 hole)
H
D
Hole centre
I
Align the scale with the line.
J
Insert scale.
K
3.2.2. Drilling the piping hole (Fig. 3-3)
► Use a core drill to make a hole of 75-80 mm diameter in the wall in the
piping direction, at the position shown in the diagram to the left.
► The hole should incline so that the outside opening is lower than the
inside opening.
► Insert a sleeve (with a 75 mm diameter and purchased locally) through the
hole.
Note:
The purpose of the hole's inclination is to promote drain flow.
3.2.3. Installing the wall mounting fixture (Fig. 3-4)
► Since the indoor unit weighs near 21 kg, selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
► The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
• The unit body must be mounted horizontally.
• Fasten at the holes marked with ▲ as shown by the arrows.
C
Min. 120 mm (617.6 mm or greater with optional drain pump installation)
A
Min. 220 mm
B
Min. 70 mm (130 mm or greater with left, rear left, or lower left piping, and optional drain
C
pump installation)
Fixing screws (4 × 25)
D
Level
E
B
Fasten a thread to the hole.
F
Place the level against the horizontal reference line of the mount board and mount so that it is
G
level. Hang a weight from the thread and align it with the ▼ mark of the mount board to make it
level.
Weight
H
Mount board
I
ACCESSORY
QUANTITY
Mount board
1
Tapping screw 4 × 25
7
Felt tape
2
L-shaped connection pipe
1
Charge nut
1
1
1
2
2
Spacer
1
1
2
1
LOCATION OF
SETTING
Fix at the back of the
unit
Make use of
packaging material

Publicité

loading

Ce manuel est également adapté pour:

Pka-m kal serie