2. Installation location
B
L
M
F
G
Fig. 2-1
(mm)
1170
A
C K
D
E
*
J
H
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and
maintenance.
A
B
Min. 100.5
Min. 52.3
Air outlet: Do not place an obstacle within 1500 mm of the air outlet.
F
Floor surface
G
Furnishings
H
When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
I
extra distance should be taken because the fan air current may create a short cycle.
1800 mm or greater from the floor surface (for high location mounting)
J
108 mm or greater with left or rear left piping and optional drain pump installation
K
I
550 mm or greater with optional drain pump installation
L
Minimum 7 mm: 265 mm or greater with optional drain pump installation
M
Warning:
• This unit should be installed in rooms which exceed the floor space specified
in outdoor unit installation manual.
Refer to outdoor unit installation manual.
• Install the indoor unit at least 1.8 m above floor or grade level.
For appliances not accessible to the general public.
• Refrigerant pipes connection shall be accessible for maintenance purposes.