OPERATING AND MAINTENANCE MANUAL
PYD SERIES SOLAR INVERTER
6.1 Parameters for pressure transducer or digital pressure gauge configuration
Parameter
Explanation
b0-02
Command source selection
Main frequency resource
b0-03
selection
C0-00
PID setting source
C0-03
PID feedback source
C3-00
Target pressure setting
The maximum value of
C3-01
feedback pressure
The project pressure of
C3-03
explosion-proof pipe
C3-04
Wakeup pressure
C3-07
Sleeping frequency
If it don't need sleeping mode, please set:
C3-04 = 100
C3-07 = 0
www.proindecsa.com / proindecsa@proindecsa.com
Remote pressure
gauge
Default
0.200
1.000
1.500
80.0%
20.00 Hz
Pressure transducer
Setting value
0
0
1
8
0
7
0
-
Adjust according
to the applications
41
Remark
0. board control
1. external terminal control
PID control
C3 group pressure control
The remote gauge set to 0.
The pressure transmitter
set to 1
Unit: Mpa
Ej: Target pressure is
0.5Mpa, wakeup pressure is
0.5MPa*80% = 0.4MPa.
This value setting set to 1
or 2Hz more than the value
there is no one to open
faucet of water pipe