2.3
Operating temperature range
Room temperature
Cooling
17 °C ... 32 °C
Heating
0 °C ... 30 °C
Dehumidifying
10 °C ... 32 °C
Table 7 AC166i... W/AC176i.3 ... W
Room temperature
Cooling
16 °C ... 32 °C
Heating
0 °C ... 30 °C
Dehumidifying
10 °C ... 32 °C
2.4
Information on refrigerant
This device contains fluorinated greenhouse gases as refrigerant. The
unit is hermetically sealed. The following information on the refrigerant
complies with the requirements of EU Regulation No. 517/2014 on
fluorinated greenhouse gases.
Product type
Rated cooling
output
[kW]
AC-4,1 MS
3.52
AC-5,3 MS
5.28
AC-6,2 MS
7.03
AC-7,9 MS
8.79
AC-8,2 MS
10.55
AC-10,6 MS
10.55
AC-12,3 MS
12.02
1) Total pipe length L in metres (if L > 5 m simple path from outdoor unit to indoor unit).
Table 9 F-Gas
3
Operation and maintenance
CAUTION
Danger due to electric shock or moving parts
▶ Disconnect the power supply before carrying out any maintenance
work.
▶ Have any maintenance steps that are not listed here carried out by an
approved installer.
HIntended use
The indoor unit is intended for installation inside the building with
connection to an outdoor unit and further system components, e.g.
controls.
The outdoor unit is intended for installation outside the building with
connection to an indoor unit or units and further system components,
e.g. controls.
The air conditioning system is intended for commercial/residential use
only where temperature deviations from adjusted set points do not lead
to damage of living beings or materials. The air conditioning system is
not suitable to set and maintain desired absolute humidity levels
precisely.
Any other use is considered inappropriate. Any damage that may result
from misuse is excluded from liability.
Logacool AC ... MS – 6721852540 (2024/06)
Outside temperature
-15 °C ... 50 °C
-15 °C ... 24 °C
0 °C ... 50 °C
Outside temperature
-15 °C ... 50 °C
-15 °C ... 24 °C
0 °C ... 50 °C
Rated heating
Refrigerant
output
Type
[kW]
3.81
R32
5.57
R32
7.62
R32
9.38
R32
11.72
R32
11.72
R32
13.48
R32
Table 8 AC166i...MS D/AC166i... MS C/CC / AC166i... MS CN
The built-in protection device may prevent the appliance from operating
at temperatures outside the above range.
If the humidity is more 80 %, condensation may form at the air
outlet. To prevent this, open the vertical ventilation flaps as wide as
possible (vertical relative to the ground) and set a high fan output.
Notice for the user: If your installer adds refrigerant, he enters the added
fill volume and the total amount of the refrigerant in the following table.
Global
CO
Initial
2
warming
equivalent
charge
potential
of initial
volume
(GWP)
charge
[kg]
[kg Co
2
equ.]
675
0.49
0.72
675
0.78
1.15
675
1.01
675
1.35
675
1.62
675
1.62
675
1.89
For installation at special locations (underground garage, mechanical
rooms, balcony or at any semi-open areas):
▶ First refer to the requirements for the installation site in the technical
documentation.
You can find information on operating the indoor units in the
corresponding operating instructions.
3.1
Operating mode conflict
When using multi-split air conditioners, all operating modes are
possible, but with the following special features:
If you operate more than one indoor unit, indoor units may go into
standby due to an operating mode conflict. An operating mode conflict
occurs when at least one indoor unit is in heating mode and at least one
indoor unit is in another operation mode at the same time (e.g. cooling
mode). Heating mode always has priority. All indoor units that are not in
heating mode go into standby due to the operating mode conflict.
Indoor units with operation mode conflict show "−−" in the display or the
ON indicator flashes and the timer indicator is on. See technical
documentation of the indoor unit for more information.
Operation and maintenance
Additional fill
Total charge
volume for
volume during
pipe length
commissioning
1)
L
[g/m]
12
12
1.5
12
2.0
24
2.4
24
2.4
24
2.8
24
3
[kg]
9