1. Fit the Installation Plate
1.
Fit the installation plate
tion plate.
2.
If the wall is made of brick, concrete or the like, drill eight (8) 5mm diameter holes in the wall. Insert
Clip anchor
3.
Fit the installation plate
90
NOTE
Fit the Installation Plate and drill holes in the wall according to the wall structure and
corresponding mounting points on the installation plate. (Dimensions are in "mm" unless
otherwise stated)
40
Over 12 cm from the wall
133
Left rear side refrigerant
2. Drill a hole in the wall
1.
Determine hole positions according to the diagram detailed in Fig.5. drill one (1) hole ( 65mm) slanting
slightly downwards to outdoor side, this will prevent water to come indoors.
2.
Always use wall hole conduit when drilling metal grid, metal plate or the like.
3. Connective pipe and drainage installation
1.
Always run the drain hose sloping downward all the way. Do not install the drain hose as illustrated
below.
4
56
horizontally on structural parts of the wall with spaces around the installa-
for appropriate mounting screws
on the wall with eight (8) type "A" screws
70
70
750
Indoor unit outline
Installation plate
920
pipe hole Ø65
A:780 (< 4.6 kW model)
Wall
Indoor
≥5°
Fig. 6
.
150 mm or more to ceiling
Installation plate
50
920 (4.6 kW ≤ model < 6.1 kW)
Outdoor
.
Over 12 cm
from the wall
Right rear side
refrigerant pipe
hole Ø65