TCB-IFDMR01UP-UL
(Terminal block with relay)
Shield wire MAX. 656'2" (200 m)
Al3
Input
0 - 10 V
Al3
Input
Name
AI3
Set temperature changed
AI4
Nothing
Analog Input 2 (DC 0 - 10 V)
TA type
Set temp
10.00
Heating / Cooling
84°F / 84°F
9.70
82°F / 82°F
8.95
81°F / 81°F
8.20
79°F / 79°F
7.45
77°F / 77°F
6.70
75°F / 75°F
5.95
73°F / 73°F
5.20
72°F / 72°F
4.45
70°F / 70°F
3.70
68°F / 68°F
2.95
66°F / 66°F
2.20
65°F / 65°F
1.45
65°F / 65°F
0.70
0.00
Locally procured
0 - 10 V Signal (+)
GND (-)
• To use this control, set DN [4A9] = 1.
• For TA and TF type, the set temperature can be changed
according to the 0 - 10 V input of AI3.
• In the set temperature with the remote controller and this
control, the post-setting is prioritized.
• The set temperature can be changed only for cooling and
heating operations.
Cannot be used.
(V)
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
1.25
0.50
– 14 –
✓ : Available
Description
TF type
Set temp
10.00
Heating / Cooling
86°F / 77°F
9.70
84°F / 75°F
8.95
82°F / 73°F
8.20
81°F / 72°F
7.45
79°F / 70°F
6.70
77°F / 68°F
5.95
74°F / 66°F
5.20
73°F / 65°F
4.45
72°F / 63°F
3.70
70°F / 61°F
2.95
68°F / 59°F
2.20
66°F / 57°F
1.45
65°F / 55°F
0.70
0.00
✕ : Prohibition
TA
DDC
TF
✓
✕
✓
-
-
-
(V)
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
1.25
0.50