ATTENTION
Do not use either hot water or any pointed, cutting, metal objects to remove ice blocks.
3.
4.
check microdoor connection keeping in mind that the switch contact must be closed when
the door is closed.
Unsatisfactory efficiency of the unit:
If no defects are found in the unit check that: cold room doors are perfectly tight; there is no
cold dispersion; the cold room is used wisely; no unfrozen liquids or foodstuffs are placed in
the low temperature room; the evaporator is ice-free.
We recommend installation of the machines far from the doors especially when the cold room
is expected to be opened many times a day.
WARNING:
Removal of protections during machine operation is absolutely forbidden. They have
been developed to safeguard the operator's safety.
12.4 Alarms
When an alarm condition occurs the following warning devices are activated (depending on
the nature of the alarm):
The buzzer and the alarm relay can be muted by pressing any key. When a key is pressed,
the led flashes as long as the alarm condition is
displayed, press ENTER key: AL appears. Press ENTER key. At this point a code is displayed
indicating the cause of the alarm.
To leave the alarm menu wait 15 seconds or press SET as long as cold room temperature is
displayed.
ALARM
High temperature
Low temperature
Room sensor
30
- faulty defrost heater (in models with electric defrost);
- faulty defrost process. In this case some measures can be taken:
increase defrost termination temperature by some degrees, increase number of
defrosts.
Display does not light up. Check:
- if there is power to the unit;
- if mains cable is connected properly;
- fuses inside the electric panel
Unit does not start operating when pressing ON/OFF key (the display is turned on):
alarm led
buzzer
alarm relay.
DISPLAY
(AH1)
Red led and alarm relay are
activated; HI is displayed
the alarm menu as indicated
above.
(AL1)
Red led, buzzer and alarm relay
are activated; AL1 is displayed
in the alarm menu.
(E1)
Red led, buzzer and alarm relay
are activated; E1 is displayed.
present.
CAUSE
Excessive door openings
Excessive product load
in
Product too warm
Malfunction of the unit
Malfunction
of
electronic controller
Faulty sensor
Sensor with wrong
connection
To have the alarm code
REMEDY
the
Service intervention
Replace sensor