Télécharger Imprimer la page

Panasonic WH-SXC09D3E8 Mode D'emploi page 7

Masquer les pouces Voir aussi pour WH-SXC09D3E8:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 12
ADVANCE OPERATION
• It is strongly recommended to contact the nearest authorized dealer to change the water temperature range.
• Using the control panel could set the temperature range for water outlet temperature and outdoor ambient temperature.
SYSTEM SETTING MODE
SETTING
SET
SELECT
CANCEL
SET
1. Press
for 5 seconds to enter "SETTING" mode. "SETTING" indicator is ON.
2. Press
or
to choose a parameter.
3. After selecting the desired parameter, press
4. Press
or
to set the desired temperature.
SET
5. Press
again to confi rm the setting.
• Repeat steps 2 to 5 to set other parameters.
Operation
Parameter * Description
Mode
HEAT
HEAT
HEAT
HEAT
HEAT
OFF
HEATER
ON
COOL
TANK
WATER TEMPERATURE THERMO SHIFT SETTING
SET
1. Press
within 5 seconds.
• Repeat steps 3 to 5 to set the desired shift temperature (-5°C ~ 5°C).
Notes:
CANCEL
• Press
or wait 30 seconds to exit "SETTING" mode.
• The setting temperature will be stored in the system once confi rm.
• "SETTING" mode cannot be activated when the "SERVICE" and "STATUS" indicator is ON.
Operation Mode
Temperature display
TIMER
OUTDOOR
HEAT
COOL
TANK
ON
QUIET
HEATER
FORCE
OPERATION
WATER OUTLET
Parameter *
SETTING indicator
SELECT
to enter the parameter.
Low outdoor ambient set temperature
(-15°C ~ 15°C).
High outdoor ambient set temperature
(-15°C ~ 15°C).
Water outlet set temperature at low
outdoor ambient temperature (25°C ~ 55°C).
Water outlet set temperature at high
outdoor ambient temperature (25°C ~ 55°C).
Set temperature for turning OFF heating operation (5°C ~ 35°C).
Outdoor ambient set temperature for turning ON heater operation (-15°C ~ 20°C).
Water set temperature during cool mode (5°C ~ 20°C)
Sanitary tank set temperature (40°C ~ 75°C).
ACTUAL
HEATER
BOOSTER
C
DEFROST
SETTING
STATUS
SERVICE
Water Temperature
Outdoor Temperature
7

Publicité

loading