SPECIFICATIONS
Operating Ambient Temperature Range:
45 to 88°F (7.2 to 32°C).
Display Range:
0 to 99°F (-18 to 37°C).
Sensor Accuracy:
+/-1.5°F at 70°F (+/-.84 at 21°C)
Operating Relative Humidity:
5% to 95% non-condensing.
Finish:
White.
Dimensions in in. (mm):
2-3/4 (70) wide x 4-5/8 (117) high x 1-1/6 (27) deep.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
® U.S. Registered Trademark
Copyright © 2004 Honeywell International Inc. •
Indoor Temperature Sensor
(USE WITH TH8000 AND TH7000 THERMOSTATS)
• All Rights Reserved
C7189 Wall Mount
INSTALLATION INSTRUCTIONS
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting
wiring.
Location and Mounting (Fig. 1)
1. Choose a location for mounting the sensor on an
inside wall about 5 ft (1.5m) above the floor. A
horizontally-mounted standard 2 x 4 in. (51 x 102
mm) junction box can also be used.
2. Be sure wire distance between C7189 and
thermostat is less than 200 feet.
3. Make sure there is good air circulation at
average temperature at the chosen location. Avoid
the following locations because they can introduce
errors in sensor measurements. See Fig. 1.
a. Hot areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from fireplaces or other heat
sources.
(c) Convection or radiant heat from the sun
or electrical equipment.
b. Cold areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from windows and doors.
(c) Unheated areas on the other side of the
wall location.
c. Dead air areas:
(a) Behind doors, furniture and curtains.
(b) In corners and alcoves.
4. Mark the area on the wall selected for mounting the
C7189 Sensor or junction box.
5. Run wire cable to a hole at the selected wall
location. Pull approximately three inches of wire
through the opening. Color-coded, 18-gauge
thermostat wire is recommended.
69-1710EFS