C7189 WALL MOUNT INDOOR TEMPERATURE SENSOR
Table 1. Sensor Resistance at Room Temperature.
Room Temperature
°F
40
4.4
42
5.6
44
6.7
46
7.8
48
8.9
50
10.0
52
11.1
54
12.2
56
13.3
58
14.4
60
15.6
62
16.7
64
17.8
66
18.9
68
20.0
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
69-1710EFS G.H. 03-04
Ohms of
°C
Resistance
22537
21516
20546
19626
18754
17926
17136
16387
15675
14999
14356
13743
13161
12607
12081
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
Table 1. Sensor Resistance at Room Temperature.
Room Temperature
°F
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Ohms of
°C
Resistance
21.1
11578
22.2
11100
23.3
10644
24.4
10210
25.6
9795
26.7
9398
27.8
9020
28.9
8659
30.0
8315
31.1
7986
32.2
7672
33.3
7372
34.4
7086
35.6
6813
36.7
6551
37.8
6301
www.honeywell.com/yourhome