3.2
RAIN SENSOR
ACTIVE ALARM when
The sensitive surface of the sensor
detects any drops of water.
3.3
SNOW CONDITION
To manage the alarm associated with snow, the temperature (NTC 10K/3435K) and the rain sensors must be combined.
ALARM ACTIVATED when
The measured temperature is below 2 °C and
rain has been detected.
Warning: if the temperature probe contact (13-14) is open (not connected) and the alarm is triggered, the control unit tilts the slats of the pergola to 66% of the
full opening with intermittent movements.
3.4
ACTIVATION/DEACTIVATION RAIN SENSOR OR SNOW CONDITION (RAIN+TEMPERATURE)
Sensor deactivation (60 minutes)
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s.
The buzzer emits 2 beeps.
3.5
TEMPERATURE SENSOR
The temperature sensor (NTC 10K/3435K) activates whenever there is danger of ice forming.
ALARM ACTIVATED when
The measured temperature is below 2 °C .
Once ACTIVE ALARM
The control unit moves the louvres to the complete closing and
it doesn't execute any command. LR is ON.
What happens with ALARM ACTIVATED
The control unit tilts the slats to 66% of full opening. The control
unit only executes hold-to-run commands.
STOP
(10 s)
What happens with ALARM ACTIVATED
The control unit tilts the pergola slats to 10% of full opening.
LR ON
DEACTIVATED ALARM when
The sensor doesn't detect any drop.
LR flashes
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or rain is
no longer detected. When the control unit receives a
command for automatic movement by transmitter, it
exits the alarm status.
Sensor activation
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s. The buzzer
emits a continuous sound.
15
Factory setting
ACTIVATED
Factory setting
DEACTIVATED
STOP
(10 s)
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or
any command is received
continuous
sound
t
°