4.3. DIMENSIONS

L
B
K
H
D
Weight
5. BOARD LAYOUT
5.1. TERMINALS
U
Power supply
0
S
Generator voltage sensing
0
+
Output (to the exciter
-
field)
60
60Hz mode selection
Hz
P
Connection to external
Q
control device
Connection to ground of
internal EMI filter
5.2. POTENTIOMETERS
Setup of generator voltage.
VOLT
Normally the internal potentiometer VOLT permits to adjuste the voltage in a wide range;
to obtain a finer possibility of voltage setting or to adjust the voltage from the control
MIN
MAX
panel, or in order to limit the voltage range, an external potentiometer can be connected
to the terminals P and Q (resistance about 100 k , 1 W, for a voltage regulation of ±5%).
Turn clockwise to increase voltage
963857121_M
149mm
89mm
132mm
41mm
6.5mm
320g