INSTALLATION
Electrical connection
Warning!
1
2
All electrical work should be carried out by a
suitably qualified and authorised electrician.
No alterations or wilful changes in the elec-
tricity supply should be carried out.
Fitting guidelines
The cooker is manufactured to work with
three–phase alternating current (400V
3N~50Hz). The voltage rating of the cooker
heating elements is 230V. Adapting the
cooker to operate with one-phase current
is possible by apropriate bridging in the
connection box according to the connection
diagram below. The connection diagram is
also found on the cover of the connection box.
Remember that the connection wire should
match the connection type and the power
rating of the cooker.
The connection cable must be secured in a
strain–relief clamp.
Warning!
Remember to connect the safety circuit to the
connection box terminal marked with
. The
electricity supply for the cooker must have a
safety switch which enables the power to be
cut off in case of emergency. The distance
between the working contacts of the safety
switch must be at least 3 mm.
Before connecting the cooker to the power
supply it is important to read the information
on the data plate and the connection diagram.