35
2
1
38
Attention!
It is critical that any enclosure is sized and selected to accomodate
and dissipate heat rise generated from all installed devices.
The table (right) provides maximum permissible heat dissipation for
each golf enclosure size. Please ensure that you calculate internal
heat generated from your installation and select the correct
enclosure accordingly.
Hager Industrial de Envolventes S.A., Alfred Nobel 18, 08430 LA ROCA DEL VALLES, SPAIN
36
a
b
VZ788N
39
37
VZ787N
1
90°
Admissible thermal dissipation loss for wall mounted
distribution boards at temperarture rise ∆T*
Reference
10K
15K
VS112..
4,3
7,1
VS212..
5,6
9,2
VS312..
6,9
11,4
VS412..
8,5
14,0
VS118..
5,8
9,5
VS218..
7,4
12,3
VS318..
9,1
15,0
VS418..
10,1
16,8
*) ∆T is the temperature difference between the upper limiting
temperature of the installed equipment and the ambient air
temperature of the distribution board.
3
2
20K
25K
30K
10,1
13,3
16,7
13,2
17,4
21,8
16,3
21,5
27,0
20,0
26,4
33,1
13,7
18,0
22,6
17,6
23,2
29,1
21,5
28,3
35,6
23,7
33,1
40,9
05