Certification
Certificate Nos: •
•
•
•
Protection:
•
•
•
•
Standards:
•
•
•
•
•
•
•
•
Specific Conditions of Use
1.
The Modular Audible Device enclosure incorporates a sinter and the volume is greater than 100 cm
of the Modular Audible Device in carbon disulphide gas atmospheres is not permitted.
2.
The Modular Audible Device has external non-metallic surfaces that may provide an electrostatic charging hazard.
3.
The Modular Audible Device has metallic components in the non-metallic walls of the enclosure, which can store
electrical charge and therefore may provide a potential electrostatic discharge. The metallic brass inserts have a
capacitance of 24 pF.
4.
When multiple Ex e terminal housings are installed, they must be fully supported by the base fixings provided.
cULus Zone Certifications
This equipment is for use in Class I, Zone 1, and Zone 21 hazardous (classified) locations. It has been investigated with
reference to risks to life and property and for conformity to the installation and use in provisions of Articles 505 and 506
of NFPA 70 (NEC).
These models use protections:
•
Class I, Zone 1, AEx db IIC T4 Gb or AEx db eb IIC T4 Gb
•
Zone 21, AEx tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)
•
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb
•
Ex tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)
Unpacking the Device:
damaged, do not attempt to install, and contact Federal Signal Customer Support.
Creating Combination Fixtures in the Field
The Federal Signal Global Series Ex de products can be connected together in the field using interchangeable E-box end
caps and a proprietary coupling system.
The proprietary coupling system allows for simple and cost-effective wiring from product to product, often eliminating
the need for expensive Ex wiring practices and Ex rated glands. The E-box is available only when factory installed on
an Ex d unit or when used as an E-box spacer adjoining an existing E-box. Please refer to the accessories listed on
page 11 for available options. When creating certain fixture combinations, it is necessary to replace E-box end caps
before mounting the product. If you are creating combination fixtures, refer to instruction manual 25500259 for specific
instructions and details.
2
ATEX Cert No.: Baseefa15ATEX0155X
IECEx Cert No.: IECEx BAS 15.0104X
UKEX Cert No.: SGS23UKEX0086X
ATEX coding:
II 2 G D
Ex db IIB T5 Gb or Ex db e IIB T5 Gb
Ex tb IIIC T100°C Db IP66
(Tamb= -55°C to + 49°C)
Ex db IIC T4 Gb or Ex db e IIC T4 Gb
Ex tb IIIC T135°C Db IP66
(Tamb= -55°C to + 70°C)
EN60079-0:2018
EN60079-1:2014
EN IEC 60079-7:2015+A1:2018
EN60079-31:2014
IEC60079-0:2017 7th Ed
IEC60079-1:2014-06 7th Ed
IEC60079-7:2017 5.1 Ed
IEC60079-31:2013 2nd Ed.
After unpacking the device, examine it for damage and verify parts. If a part is missing or
; therefore, use