In spaces with combustion devices
• Install the CO detector at 1 to 3 meters away from combustion devices,
within the air flow from the combustion device and preferably on the
ceiling.
• Install the CO detector way from of roof ridges, corners. arched ceilings or
front roofs.
• In the case of smaller spaces (<4m³), the detector should be installed
outside these spaces.
• Install the CO detector 60 centimeters from surrounding walls and
ceilings. Installation on a ceiling is recommended in rooms with a
combustion device.
> 60 cm
1 - 3 m