Models 154X-024*-CN
and 154XSTHI
Strobe Light for Use in Harsh Environments/
Hazardous Locations
256294 Rev B2 0323
Limited Warranty: This product's limited warranty can be
found at www.fedsig.com/SSG-Warranty.
SAFETY MESSAGES TO INSTALLERS AND USERS
It is important to follow all instructions shipped with
this product. This device is to be installed by a trained
electrician who is thoroughly familiar with the National
Electrical Code, NFPA72, and the Canadian Electrical Code
and ULC-S524, the Standard for the Installation of Fire
Alarm Systems, and will follow the NEC Guidelines as well
as local codes.
The selection of the mounting location for the device,
its controls, and the routing of the wiring is to be
accomplished under the direction of the facilities engineer
and the safety engineer. Listed below are some other
important safety instructions and precautions you should
follow:
Read and understand all instructions before
installing or operating this equipment.
Do not connect this light to the system when power
is on.
After installation, ensure that the set screw is
properly tightened and that threaded joints are fully
engaged.
After installation, test the light system to ensure that
it is operating properly.
After testing is complete, provide a copy of this
instruction sheet to all operating personnel.
Establish a procedure to routinely check the light
installation for integrity and proper operation.
Failure to follow all safety precautions and instructions
may result in property damage, serious injury, or death to
you or others.
General — The Model 154XSTHI Strobe Light is a UL
listed visual signal for hazardous locations. The effective
candlepower (ECP) of the light is 17 cd with guard and
25 cd without guard.
The Model 154XST-024*-CN Strobe Light is a ULC listed
visual signal for hazardous locations (*denotes lens color:
A,B,C,G,R). See Table 2 for fire and light output ratings.
The Model 154XST Series provides 60 high-intensity
flashes per minute. The light is rated for 24 Vdc regulated.
This light is also rated to be installed in a low ambient
:
temperature of –55°C. For the dispersion pattern of the
clear lens Model 154XST Series, see Figure 1.
Degrees
Light Intensity (cd)
Min. per ULC-S526
(with Guard)
0
17.0
5
15.3
10
15.3
15
15.3
20
15.3
25
15.3
30
12.8
35
12.8
40
12.8
45
12.8
50
9.4
55
7.7
60
6.8
65
6.0
70
6.0
75
5.1
80
5.1
85
4.3
90
4.3
Figure 1 Dispersion
ON AXIS HORIZONTAL
EN EL EJE HORIZONTAL
SUR L'AXE HORIZONTAL
90∞
90∞
75∞
75∞
60∞
60∞
45∞
45∞
30∞
30∞
15∞
0∞ 15∞
290A4167C
Light Intensity (cd) Min. per
ULC-S526
(without Guard)
25.0
22.5
22.5
22.5
22.5
22.5
18.8
18.8
18.8
18.8
13.8
11.3
10.0
8.75
8.75
7.5
7.5
6.25
6.25

Publicité

loading

Sommaire des Matières pour Federal Signal 154X-024 CN Serie

  • Page 1 Models 154X-024*-CN and 154XSTHI Strobe Light for Use in Harsh Environments/ Hazardous Locations 256294 Rev B2 0323 Limited Warranty: This product’s limited warranty can be The Model 154XST Series provides 60 high-intensity found at www.fedsig.com/SSG-Warranty. flashes per minute. The light is rated for 24 Vdc regulated. This light is also rated to be installed in a low ambient SAFETY MESSAGES TO INSTALLERS AND USERS temperature of –55°C.
  • Page 2 USCG (CFR46) missing or damaged, do not attempt to install the device. Sections (110-113). Contact Federal Signal Customer Support. The Model 154XST has provisions for mounting to 3/4" pipe and may be mounted in any position. Before mounting, ensure that mating threads are clean.
  • Page 3 Team at +1 708-587-3587 or signalsupport@fedsig.com. Repair Service: A return authorization is required. Contact FIRE HAZARD: To prevent ignition of hazardous your Authorized Distributor or Federal Signal Customer atmospheres, disconnect the fixture from the supply Support. Defective products under warranty will be circuit before opening.
  • Page 4 2645 Federal Signal Drive, University Park, Illinois 60484 Additional translations available at signaling.fedsig.com Traducciones adicionales disponibles en signaling.fedsig.com Customer Support 1-800-344-4634+1-708-534-4756, iordersup@fedsig.com Technical Support 1-800-755-7621+1-708-587-3587, signalsupport@fedsig.com signaling.fedsig.com...
  • Page 5 Modéles 154X-024*-CN et 154XSTHI Feu à éclats pour utilisation en conditions difficiles / endroits à risque 256294 Rev B2 0323 Garantie limitée : La garantie limitée de ce produit peut être La série modèle 154XST fournit 60 flashs à haute intensité consultée sur le site www.fedsig.com/SSG-Warranty.
  • Page 6 être conforme à la norme USCG (CFR), n’essayez pas de l’installer et contactez l’assistance sections (110-113). clientèle de Federal Signal. Le modèle 154XST est prévu pour le montage avec des tuyaux de 3/4 de po et peut être installé dans n’importe quelle position.
  • Page 7 Service de réparation : Une autorisation de retour est D’ENTRETIEN Voici une liste d’instructions et de précautions de sécurité requise. Contactez votre distributeur agréé ou l’assistance clientèle de Federal Signal. Les produits défectueux sous importantes à respecter : garantie seront réparés ou remplacés à la discrétion de •...
  • Page 8 Systèmes de sûreté et de sécurité 2645 Federal Signal Drive, University Park, Illinois 60484 Traductions supplémentaires disponibles sur signaling.fedsig.com Traducciones adicionales disponibles en signaling.fedsig.com SCANNEZ MOI Support client 1-800-344-4634+1-708-534-4756, iordersup@fedsig.com Support technique 1-800-755-7621+1-708-587-3587, signalsupport@fedsig.com signaling.fedsig.com...

Ce manuel est également adapté pour:

154xsthi