Télécharger Imprimer la page

TDK-Lambda ZMS10015 Mode D'emploi page 14

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 5
ZMS100 Handbook
Level of Insulation:
Dielectric Strength type testing is carried out as follows:
Primary mains circuit to earth: 2.5 - 2.6 kVdc.
Primary mains circuits to secondary: 4.25 - 4.35kVdc
Secondary circuits to earth: 2.5 - 2.6 kVdc.
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC / EN60950-1 – CE mark.
CE marking when applied to any ZMS100 product, indicates compliance with the Low Voltage Directive
(2014/35/EU) in that it complies with EN60950-1, and with Directive 2011/65/EU of the European Parliament
and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical
and electronic equipment.
IEC/EN 60950-1, and IEC/EN 60601-1 - CB Report and Certificate
UL/CSA 60601-1/ANSI/AAMI ES 60601-1 - UL + C -UL approval
IEC/EN 60335 – Test report.
Fusing:
Internal fuses (F1 and F2): in the L and N line, T3.15AL, 250V, Symbols:
AC
EARTH
Caution: See instructions for use
Unit Nomenclature
ZMS100 models as described below:
Units may be marked with a Product Code: ZMSx where x may be any number of characters. Unit
Configuration Code (Description): may be prefixed by NS # followed by / or - (where # may be any
number of characters indicating non- safety related model differences). Unit Configuration Code:
Nomenclature for ZMS100
Units may be marked with a Product Code:- ZMS-X/T/J followed by any number of characters indicating non-
safety related model differences.
Unit Product Code (Description) may be prefixed by SP and/or NS # followed by / or - (where # may be any
number of characters indicating non-safety related model differences).
Where:
-X
=
/T
=
/J
=
Input Parameters
Parameter
Nominal input voltage
Input voltage range
Input frequency range
Maximum input current
* Units are rated for 47 – 63Hz but will operate up to 440Hz.
All ratings apply for ambient temperatures up to 50°C. From 50 to 70°C the total output power and current
ratings are both derated at 2.5% per deg C.
N
Neutral
Output Voltage as detailed in the Output Parameters Tables below.
Earth fast-on terminal not fitted
JST input and/or output connectors fitted
60601-1
100 - 240 Vac
85 - 264Vac
47 - 63Hz
2.2A rms
L
Live
60950-1/61010-1
100 - 240 Vac
85 - 264Vac
47 - 440Hz*
2.2A rms
Page 14 of 22
Warning: Dangerous Voltage
260153 issue 8, February 2017

Publicité

loading

Ce manuel est également adapté pour:

Zms100Zms10048Zms10036