Télécharger Imprimer la page

Balluff BAE00ZU Notice D'utilisation page 10

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 12
Instruction manual BAE SA-XE-051-XR
Dimensions
Connection diagram
eigensicherer zertf. Sensor nach
intrinsically safe sensor accord. to
NAMUR, DIN EN 60947-5-6 /
IEC 60947-5-6
Function display and controls
green
yellow
Programming
switch
Programming
The function of the output circuit is determined by
the programming switch.
* State defined in IEC 60947-5-6
BA-S36066-GB-2018-10
explosionsgefährdeter
Bereich
hazardous area
(+)
(–)
BAE00ZU
PWR
OUT
red
CHK
NO
NC
NO
NC
nichtexplosionsgefährdeter Bereich
non hazardous area
BAE SA-
1 (+)
XE-051-XR
2 (–)
Marking
LED
Specification
CHK
red
lights up with cable break
or short circuit
OUT
yellow lights up when the relay is energized
PWR
green
Supply voltage connected
Switch position NO
Input (1,2)*
Relay output (9,10,12)
12-9
conductive
closed
non-conductive
open
Switch position NC
Input (1,2)*
Relay output (9,10,12)
12-9
conductive
open
non-conductive
closed
Page 3
Betriebsspannung
+
15
Supply voltage
16
24 V DC ±10%
10
Relais-Ausgang
9
Relay output
12
F: 5 A (F)
nach / according to
IEC 60127
12-10
open
closed
12-10
closed
open

Publicité

loading

Ce manuel est également adapté pour:

Bae sa-xe-051-xr