5 Electrical wiring
5.4 ELECTRICAL CONNECTION OF THE INDOOR UNIT
C A U T I O N
Check to ensure that the field supplied electrical components (ma-
ins power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and
local codes. If it is necessary, contact with your local authority in
regards to standards, rules, regulations, etc.
5.4.1 Wiring size
Use wires which are not lighter than the polychloroprene sheathed
flexible cord (code designation 60245 IEC 57).
Power
Model
current
supply
RPI-16.0FSN3PE
1~ 230V
50Hz
RPI-20.0FSN3PE
5.5 TRANSMISSION WIRING BETWEEN OUTDOOR AND INDOOR UNIT
The transmission is wired to terminals 1-2.
The H-LINK II wiring system requires only two transmission cables that connect the indoor unit and the outdoor unit.
Use twisted shielded pair cable or shielded pair cable for transmission wires between the indoor and the outdoor units, and connect
the shielded part (only one side) to the earth screw in the electrical box of the indoor unit.
In the event that a conduit tube for field-wiring is not used, fix rubber bushes to the panel with adhesive.
C A U T I O N
Ensure that the transmission wiring is not wrongly connected to any live part that could be damaged the PCB.
5.6 SETTING OF REMOTE CONTROL SWITCH
This unit is factory set with the Optional Function: Output Signal
o2 02 "Alarm Signal" activated.
Screenshot of the Remote Control Switch
9
PMML0323A rev.2 - 06/2014
Power
Transmiting
Max.
supply
cables
cables
(A)
EN60335-1
EN60335-1
2 x 4.0 mm²
16.2
+ GND
2 x 0.75mm
2 x 4.0 mm²
17.7
+ GND
1
1
5.4.2 Minimum requirements of the protection devices
C A U T I O N
Ensure specifically that there is an Earth Leakage Breaker
(ELB) installed for the units.
If the installation is already equipped with an Earth Leakage
Breaker (ELB), ensure that its rated current is large enough to
hold the current of the units.
N O T E
Electric fuses can be used instead of magnetic Circuit Break-
ers (CB). In that case, select fuses with similar rated values
as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual
is also commonly known as Residual Current Device (RCD) or
Residual Current Circuit Breaker (RCCB).
2
The Circuit Breakers (CB) are also known as Thermal-Mag-
netic Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Power
Model
supply
RPI-16.0FSN3PE 1~ 230V
RPI-20.0FSN3PE
MC: Maximum current; CB: Circuit breaker; ELB: Earth leakage
breaker
2
Indoor unit
2
Outdoor unit
C A U T I O N
Make sure that this configuration is set after installing / wiring the
indoor unit. If not, set this Optional Function as indicated above.
Applicable
voltage
MC
CB
U
U
(A)
(A)
max.
min.
(V)
(V)
16.2
20
207
253
50Hz
17.7
20
ELB
(nº poles/A/
mA)
2/40/30