Télécharger Imprimer la page

Carel thTx Mode D'emploi page 18

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ENG
Serial interface
RS485 serial interface for communication with the controllers. Use AWG
20 to 22 shielded wire. The total length of the network must not exceed
500 m. The power supply wires must be between 0.5 mm
Up to 32 terminals can be connected. For large networks, place a 120
Ohm resistor between A (RX/TX+) and B (RX/TX-) on the last device, to
avoid possible communication problems.
Exploded view
thTx 24 Vac/dc network configuration
B (-)
A (+)
GND
V+
230 Vac
24 Vac
V-
"thTx" +030220865 rel. 1.0 - 11.03.2024
2
and 1.5 mm
Fig. 1.f
thTx 1
EH
EM EL VC V0
COM
B (-) A (+)
G
V-
V+
Disassembly
Insert a screwdriver into the groove on the bottom and press outwards
to detach the display.
2
.
General notes
Avoid installing the device in environments with the following
characteristics:
• relative humidity higher than the specified value;
• strong vibrations or knocks;
• exposure to water sprays;
• exposure to aggressive and polluting atmospheres (e.g.: sulphur and
ammonia gases, saline mist, smoke) which may cause corrosion and/
or oxidation;
• strong magnetic and/or radio frequency interference (thus avoid instal-
lation near transmitting antennae);
• exposure to direct sunlight and the elements in general;
• wide and rapid fluctuations in room temperature;
• environments where explosives or flammable gas mixtures are present;
• exposure to dust (formation of corrosive patina with possible oxidation
and reduction of insulation).
thTx 2...
EH
EM EL VC V0
COM
B (-) A (+)
G
V- V+
Fig. 1.g
8
...thTx 32
EH
EM EL VC V0
COM
B (-) A (+)
G
V- V+
120 Ω

Publicité