FLOOR PROTECTOR
Your wood stove should be placed on a 1 inch, non-combustible surface with a k factor of 0.84. For multiple
layers, add R-values of each layer to determine the overall R-value. The R value for the required board is 1.03. If
there is a horizontal section of chimney connector, the floor protector should go under it and 2 inches beyond
each side To calculate R-Values for alternative methods, see "Alternate Floor Protector Calculations" section in
this manual.
The floor protector should exceed the stove as follows:
Dimension
H **
Front
J**
Left
K**
Right
L**
Back
M
Total Width
N
Total Length
* Canadian installations require 18" (457mm)
** Canadian installations require 8" (203mm)
-6-
Inch
mm
16
635
6
153
6
153
1
25
46
1169
53.5
1359