Step 3: VRP-433 Repeater Placement Testing (Interference
Detection)
Repeater placement test ensures the VRP-433 is located in an area with low noise and
interference and can successfully receive signals from one-way wireless devices.
To perform a Repeater placement test:
1. Press and hold Programming button for 1 second to enter Programming mode. The "Mode
Entered" tone sounds (1 long beep). Repeater placement test is continuously active until
Programming mode is exited, times out after 4 hours or cover is put back on unit.
2. If RF traffic level or noise floor level is too high, the yellow LED lights steadily. If this occurs,
reposition unit until yellow LED turns off.
3. To exit Enroll/Placement mode, press Programming button again for 1 second or place cover
back on VRP-433. The "Mode Exited" (3 beeps) tone sounds.
Step 4: Enrolling the VRP-433 with the Alarm Panel
The VRP-433 has a six-digit electronic serial number (ESN) that must be input to the alarm
panel during enrollment.
To manually enroll VRP-433, consult alarm panel installation manual.
NOTE: The VRP-433 repeater should be enrolled as a radio detector.
NOTE: For Absoluta Series, Kyo320 and KyoUnit, use the serial number beginning with "2."
The serial number beginning with "A" is for future use.
NOTE: if there is no mains power and the battery is flat, then the alarm will go off in the area
for which the VRP-433 has been enrolled: programme the panel for the necessary reports.
Program a zone label to identify the VRP-433. e.g.,"Rpter 1 Pwr Trbl."
Step 5: Placement Testing the VRP-433
For optimal performance between the VRP-433 and the alarm panel, the RF signal between the
two units should be as free from interference as possible.
To test the RF link between the VRP-433 and the alarm panel:
1. Place alarm panel into placement test (see panel installation instructions) and select zone
where VRP-433 is enrolled.
2. Tamper the VRP-433.
3. If alarm system indicates a weak signal or no response, check alarm panel or reposition VRP-
433 and repeat test. VRP-433 should only be placed in location where multiple good results are
received.