5.2 - MOTORE
CITY4-EVO control unit can control one alternate current
asynchronous motor. Max. total power is 700W.
Connect motor cables as follows:
• opening cable to terminal G3
• closing cable to terminal G5
• common return cable to terminal G4
G1 G2 G3 G4 G5 G6 G7
m
WARNING:
In case it has not yet fitted, a start capacitor is required.
Connect the start capacitor between terminals G3 and G5.
HYDRAULIC MOTORS
If hydraulic motors are used, it is necessary that some unit
programming parameters are set out as follows:
• Motor power set at 100%
Pot
100
=
• Slowdowns are disabled (they are already disabled by default)
rA.AP
no
=
rA.Ch
no
=
• Obstacles sensor disabled
SEnS
no
=
M
5.3 - STOP
For added safety, you can install a STOP switch that, when
pressed, immediately stops the automation.
The switch must have a normally closed contact, which opens in
case of activation.
• Connect the cables of the STOP switch between terminals
L5 (STOP) and L6 (COM) of the unit.
C
To activate the function, change the settings of
StoP
parameter
L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11
NOTE: in case the stop switch is operated while the gate is
open, the automatic closing function will always be disabled. To
close the gate again, you will need a start command (if the start
function in pause is disabled, it will be temporarily enabled to
allow the gate release).
The stop switch function can be activated by means of a remote
control stored on channel 3 (see relevant instructions of MR
receiver).
5.4 - ACTIVATION INPUTS
CITY4-EVO is equipped with two activation inputs (START
and START P.), whose operation depends on the programmed
Strt
operation modes (see
Standard mode (DEFAULT)
START = START (it controls the total opening of the gate)
START P. = START PEDONALE (it controls the partial opening of the
gate)
Open/Close command
START = APERTURA (it controls the opening of the gate)
START P. = CHIUSURA (it controls the closing of the gate)
Dead man operation
START = APERTURA (it controls the opening of the gate)
START P. = CHIUSURA (it controls the closing of the gate)
The gate is opened or closed until the contact of the START or
START P. entrance remains closed; the gate stops immediately
when the contact is opened.