Code Zone 2
3-pole + PE
3-pole +N + PE
GHG 519, 4-pole 50/60Hz
220-250V
380-415V
500V
blue
red
black
GHG 519, 5-pole 50/60Hz
220-250V
380-415V
500V
blue
red
black
Dimensions in mm
X = fixing dimensions
Wall socket
Explosion-protected plugs and sockets 125A, GHG 519
1
Technical data
1.1
Plug and socket GHG 519
Marking acc. to 94/9/EC:
EC type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
Switching capacity AC 3:
Perm. ambient temperature:
Other temperatures possible for special versions.
Perm. storage temperature in original packing:
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entry:
Wall socket
690V
Plug
black
Supply terminal:
Wall socket
Plug
Min. cross section / Supply terminal
for 125A rated current
Test torques:
Cap nut of the M63 entry
Cover screws
690V
Terminals, plug
black
Terminals, wall socket
Self-cutting screws size 5
Weight (standard version):
Wall socket
Plug
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
II 3 G
Ex nC IIC T5/T6
PTB 99 ATEX 1115
up to 690 V, 50/60 Hz
max. 125 A
max. 125 A gL without thermal protection
max. 160 A gL with thermal protection
(therm. protection set to 125A)
up to 690 V / 125 A
-20° C to +40° C (standard version)
-40° C to +80° C
IP 66 (standard version)
I - is complied with by devices
(standard version)
2 x M63 (Ø 35 - 46 mm)
Ø 21-48 mm (Ø 31-58 mm)
2 x 4 - 70 mm² (max 1x120 mm²)*
1 x 4 - 35 mm² with pin cable lugs 1x50mm²
* (use cable lugs supplied)
Observe current load !
Wall socket
1x 50mm²
Ø min. 22.0 Nm / Ø max. 5.00 Nm
2.5 Nm
4.5 Nm
6.0 Nm
3.0 Nm
4-pole
ca. 12.30 kg
ca.
0.90 kg
690 V VAC
20 A
AC 15
400V / 6 A
DC 13
24V / 2 A
Contact arrangement
4-pole
5-pole
w/o auxiliary contact
Plug
Cooper Crouse-Hinds GmbH
Plug
1x 35mm²
5-pole
ca. 13.00 kg
ca.
1.20 kg
with auxiliary contact
7 7 7 7 7